APFC Capacitor Bank Sizing: kVAr Calculation Guide

Why Power Factor Correction?

Poor power factor results in:

  • Penalty charges from electricity utility
  • Higher current draw for same kW load
  • Increased losses in cables and transformers
  • Reduced effective capacity

kVAr Calculation

Formula

kVAr required = kW × (tan φ₁ - tan φ₂)

Where:

  • φ₁ = arccos(existing PF)
  • φ₂ = arccos(target PF)

Example

  • Connected load: 500 kW
  • Existing PF: 0.75
  • Target PF: 0.99
  • kVAr = 500 × (tan(41.4°) - tan(8.1°)) = 500 × (0.882 - 0.142) = 370 kVAr

Stage Sizing

APFC panels switch capacitor stages automatically:

  • Minimum step: Usually 25 kVAr
  • Total stages: 6, 8, or 12 stage relay
  • Step ratio: Equal or 1:2:2 ratio

Standard Bank Sizes

150, 200, 250, 300, 400, 500, 600 kVAr

Detuned Reactors

For installations with harmonics (VFDs, rectifiers):

  • 7% detuned reactor (tuned to 189 Hz) for typical harmonic content
  • 14% detuned reactor for high harmonic environments
  • Prevents capacitor resonance and premature failure

APFC Relay Selection

  • Stages: 6, 8, or 12
  • Sensitivity: 0.01 (minimum step / CT ratio)
  • Response time: 30-90 seconds
  • Power supply: 230V AC